Accident Summary Nr: 997932 - ELECTRIC BURNS - CONTACT WITH ENERGIZED BUSHING

Accident Summary Nr: 997932 -- Report ID: 0551800 -- Event Date: 09/03/1986
Inspection NrDate OpenedSICNAICSEstablishment Name
10199652809/05/198649110Indianapolis Power & Light Co

Abstract: A TWO-MAN TEST CREW WAS TESTING AN OIL CIRCUIT BREAKER AT A SUBSTATION. THE CREW WAS REQUIRED TO OBTAIN PERMISSION FROM THE THE LOAD DISPATCHER BEFORE STARTING. THE CREW MANUALLY OPENED THE SWITCH BY MEANS OF AN OPERATING SWITCH HANDLE. THE FIRST EMPLOYEE REMOVED A 20-FOOT WOODEN EXTENSION LADDER FROM THEIR VAN. HE POSITIONED IT TO INSTALL THE HIGH VOLTAGE TEST LEAD ON THE FIRST BUSHING OF THE OIL CIRCUIT BREAKER. AFTER TESTING THE FIRST TWO BUSHINGS, THE EMPLOYEE ASKED THE SECOND WORKER TO PLACE THE TEST LEAD ON THE THIRD ONE. THE EMPLOYEE STATED THAT HE HEARD A NOISE AND SAW THE SECOND EMPLOYEE ON FIRE AND LEANING TOWARD THE THIRD BUSHING. ANOTHER EMPLOYEE, WHO WAS IN THE SUBSTATION YARD, HEARD THE NOISE AND ASSISTED THE FIRST EMPLOYEE IN REMOVING THE INJURED EMPLOYEE FROM THE LADDER. THE FIRST EMPLOYEE STATED THAT THE "B" PHASE BLADE ON THE BUS-SIDE DISCONNECT WAS NEVER OPENED, THUS THE JUMPER FEEDING THIS BUSHING WAS NEVER DEENERGIZED. THE INJURED EMPLOYEE WAS TAKEN TO THE BURN CENTER OF THE HOSPITAL AND DIED THE NEXT DAY. THE FIRST EMPLOYEE, WHO WAS ALSO INJURED, WAS TREATED FOR HIS BURNS AND RELEASED.

Keywords: BURN, CLOTHING, ELECTRICAL, LADDER, LOCKOUT, E PTD, SUBSTATION, CIRCUIT BREAKER, ELEC UTILITY WORK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 101996528 Fatality Foreign Body Ineye Electrical power installers and repairers
2 101996528 Non Hospitalized injury Other Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close