Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 885954 - ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

Accident Summary Nr: 885954 -- Report ID: 1050210 -- Event Date: 10/02/1991
Inspection NrDate OpenedSICNAICSEstablishment Name
10851447210/04/199149110North Slope Borough Municipal Services

Abstract: A POWER LINE WORKER CONTACTED A GROUNDED CONDUCTOR AND A 2400-VOLT CONDUCTOR AT THE SAME TIME. AS A RESULT OF THE ELECTRIC SHOCK HE RECEIVED, THE EMPLOYEE WENT INTO CARDIO-PULMONARY ARREST. HIS COWORKER REVIVED HIM, LOWERED HIM TO THE GROUND, AND APPLIED FIRST AID. THE INJURED EMPLOYEE WAS TRANSPORTED TO A HOSPITAL. THE EMPLOYEE, WHO WAS HOSPITALIZED FOR HIS INJURIES, HAD BOTH ARMS AMPUTATED AT THE ELBOW.

Keywords: BURN, ELEC PROTECT EQUIP, AMPUTATED, OVERHEAD POWER LINE, ELECTRICAL, CPR, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 108514472 Hospitalized injury Amputation Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close