Accident Summary Nr: 840579 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 840579 -- Report ID: 0521400 -- Event Date: 06/30/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
11060198607/02/199049110Commonwealth Edison

Abstract: A SQUIRREL HAD CAUSED A POWER OUTAGE AT A SUBSTATION. TO TROUBLESHOOT THE PROBLEM, A REPAIR CREW WAS ISOLATING A 138-KILOVOLT/12-KILOVOLT TRANSFORMER TO CHECK IT FOR DAMAGE. THE NEUTRAL CONDUCTOR ON THE LOW-VOLTAGE SIDE OF THE TRANSFORMER WAS CONNECTED TO THE NEUTRAL CONDUCTOR FOR THE LOW-VOLTAGE SIDE OF TWO OTHER TRANSFORMERS IN THE SUBSTATION; HOWEVER, THE NEUTRAL'S DISCONNECT SWITCH WAS LEFT IN THE CLOSED POSITION. ONE OF THE EMPLOYEES WAS ELECTROCUTED WHEN HE DISCONNECTED ONE OF THE PHASE CONDUCTOR LEADS FOR THE LOW-VOLTAGE SIDE OF THE TRANSFORMER.

Keywords: PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK, TRANSFORMER

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 110601986 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close