Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 825927 - EMPLOYEE ENTERED OXYGEN DEFICIENT CONFINED SPACE

Accident Summary Nr: 825927 -- Report ID: 0352450 -- Event Date: 11/07/1986
Inspection NrDate OpenedSICNAICSEstablishment Name
1880792511/20/198616230Ligon & Ligon, Inc

Abstract: WORKERS WERE COMPLETING A LOW PRESSURE NITROGEN TEST ON 115-KILOVOLT CONDUIT CABLES. THE FOREMAN ASSIGNED TO THIS TASK WAS TRANSFERRED TO ANOTHER JOB. THE EMPLOYEES WERE WRONGLY LED TO BELIEVE THAT A SUBSTITUTE FOREMAN WAS TO SUPERVISE THE OPERATION. AN INCORRECT PROCEDURE WAS USED IN PURGING THESE LINES. AS A RESULT, THE CONDUIT VAULTS WERE FILLED WITH NITROGEN. EMPLOYEE #1 ENTERED A VAULT TO RETRIVE SOME SAFETY CONES, AFTER NOTIFYING THE SUBSTITUTE FOREMAN. THE CONES HAD BEEN PLACED THERE THE PREVIOUS DAY. NEITHER EMPLOYEE #1 NOR THE SUBSTITUTE FOREMAN WAS AWARE OF ANY POSSIBLE HAZARDS. THE SUBSTITUTE FOREMAN AND ANOTHER WORKER WERE FOLLOWING ESTABLISHED POLICY BY FUCTIONING AS ATTENDANTS. EMPLOYEE #1 ENTERED THE VAULT AND PASSED OUT DUE TO A TRANSIENT ANOXIA CONDITION. THE ATTENDANTS INITIALLY ATTEMPTED TO RESCUE EMPLOYEE #1, BUT FOLLOWED INCORRECT PROCEDURES. THEY WERE NOT AFFECTED BY THE NITROGEN, AND WERE EVENTUALLY ABLE TO REMOVE EMPLOYEE #1 FROM THE CONFINED SPACE. THE EMPLOYEES IN THIS INCIDENT WERE NOT TRAINED ADEQUATELY TO HANDLE THE SITUATION.

Keywords: OXYGEN DEFICIENCY, RESPIRATORY, CONFINED SPACE, WORK RULES, NITROGEN, ELEC UTILITY WORK, UNTRAINED

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 18807925 Non Hospitalized injury Asphyxia Construction trades, n.e.c.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close