Accident Summary Nr: 821611 - BURN - ELECTRICAL FAULT IN PANELBOARD

Accident Summary Nr: 821611 -- Report ID: 0352440 -- Event Date: 07/29/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
1885647608/05/198717310Capitol Electric Company, Inc.

Abstract: AN ELECTRICIAN WAS USING A STEEL TAPE TO FISH AN EQUIPMENT GROUNDING CONDUCTOR THROUGH AN UNDERGROUND CONDUIT. THE 200-FOOT STEEL TAPE WAS BEING USED IN A 400-AMPERE, 480-VOLT, THREE-PHASE FOP PANELBOARD (MODEL NUMBER M3A, SERIES C). THE PANELBOARD WAS WITHIN A 1200-AMPERE, 3-PHASE, 4-WIRE, 480/277-VOLT COMPARTMENT. THE ACCESS PANEL OPENING FOR THE PANELBOARD WAS 23 INCHES WIDE AND 9.5 INCHES HIGH AND WAS ABOUT 3.5 INCHES ABOVE THE FLOOR. AN ENERGIZED BUSBAR WAS LOCATED INSIDE THE PANELBOARD, ABOUT 4 INCHES ABOVE THE OPENING. THE ELECTRICIAN WAS FEEDING THE TAPE THROUGH A 4-INCH-DIAMETER PVC CONDUIT THAT WAS ENCASED IN CONCRETE AND THAT HAD THREE, 0.75-INCH-DIAMETER CABLES IN IT. THE EMPLOYEE WAS LYING ON HIS RIGHT SIDE FEEDING THE TAPE THROUGH THE CONDUIT, AND THE TAPE HUNG UP. THE STEEL TAPE CONTACTED THE 480-VOLT BUSBAR, AND THE RESULTANT ELECTRIC ARC, EXPLOSION, AND FIRE CAUSED FIRST AND SECOND DEGREE BURNS ON THE EMPLOYEE'S LEFT ARM (FROM HIS FINGERS TO THE MIDDLE OF HIS UPPER ARM), ON THE RIGHT SIDE OF HIS NECK, AND ON THE UPPER PORTION OF HIS RIGHT ARM.

Keywords: BURN, METAL WIRE, ELECTRICAL, ELECTRICIAN, PANELBOARD, BUSBAR, ELECTRICAL WORK, E C, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 18856476 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close