Accident Summary Nr: 802439 - EMPLOYEE BURNED TRYING TO PUT OUT NATURAL GAS FIRE

Accident Summary Nr: 802439 -- Report ID: 0454510 -- Event Date: 01/09/1988
Inspection NrDate OpenedSICNAICSEstablishment Name
10542197801/19/198865130Wright Management Services

Abstract: A NATURAL GAS FIRE OCCURRED WHEN GAS LEAKING FROM A BREAK IN AN 8 INCH GAS LINE WAS IGNITED BY FLAMES IN THE BOILER FLAME BOX OR BY ELECTRICAL SHORTS IN THE WIRING LEADING TO THE BOILER. THE CAUSE COULD NOT BE DETERMINED. IN AN ATTEMPT TO EXTINGUISH THE FIRE, EMPLOYEE #1 TRIED TO CLOSE A GAS LINE HAND VALVE, BUT SUCCEEDED ONLY IN ENLARGING THE BREAK. THE GALVANIZED GAS LINE BROKE BECAUSE IT WAS NOT SUFFICIENTLY BRACED TO PREVENT MOVEMENT AND FATIGUE TO THE METAL OF THE PIPE. EMPLOYEE #1 WAS HOSPITALIZED FOR 4 DAYS WITH BURNS TO THE HANDS AND FACE.

Keywords: BURN, WORK RULES, FIRE, NATURAL GAS, GAS LEAK, FACE, HAND

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 105421978 Hospitalized injury Burn/Scald(Heat) Laborers, except construction

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.