Accident Report Detail

Accident Summary Nr: 767111 - ELECTRIC SHOCK - CONTACT WITH LIVE CONDUCTOR THRU DUCT

Accident Summary Nr: 767111 -- Report ID: 0626300 -- Event Date: 07/27/1988
Inspection NrDate OpenedSICNAICSEstablishment Name
10058525607/28/198816290Fluor Daniel Construction Co., Inc.

Abstract: A THREE-WORKER CREW WAS INSTALLING A HEATING AND AIR CONDITIONING DUCT SYSTEM IN A BATTERY CHARGING ROOM. THE DUCT WORK WAS LOCATED ABOUT 6 FEET, 9 INCHES ABOVE THE FLOOR. THE LEAD WORKER REMAINED AT GROUND LEVEL, WHILE THE OTHER TWO EMPLOYEES WERE WORKING FROM A SCAFFOLD, PERFORMING THE INSTALLATION. THREE DUCT SECTIONS HAD BEEN INSTALLED, AND THE TWO EMPLOYEES BEGAN INSTALLING THE THIRD, WHICH HAD TO BE POSITIONED ABOVE A CABLE TRAY CONTAINING ENERGIZED, BUT INSULATED, ELECTRIC CONDUCTORS. A PIECE OF 0.75-INCH-THICK PLYWOOD THAT WAS 16 INCHES WIDE HAD BEEN LAID ACROSS THE 30-INCH WIDE CABLE TRAY TO SUPPORT THE 40-INCH-BY-20.5-INCH-BY-22.5-INCH DUCT SECTION. THE BODY OF THE DUCT WAS 16 INCHES WIDE WHERE IT WAS TO BE SUPPORTED BETWEEN CEILING HANGERS THAT WERE ALSO 16 INCHES WIDE. ONE OF THE TWO EMPLOYEES REMAINED ON THE SCAFFOLD WHILE HIS COWORKER WALKED ONTO THE CABLE TRAY. THE TWO EMPLOYEES THEN MANEUVERED THE DUCT TO FIT BETWEEN THE HANGERS. THE DUCT FELL OFF THE PLYWOOD, CUTTING THE INSULATION ON A 120-VOLT CONDUCTOR. THIS ENERGIZED THE DUCT SECTION, WHICH WAS WEDGED BETWEEN THE METAL SIDE OF THE CABLE TRAY AND A PIECE OF METAL CONDUIT ATTACHED TO THE CONCRETE WALL. THE EMPLOYEE ON THE CABLE TRAY WAS SITTING OR SQUATTING ON THE SIDE RAIL OF THE TRAY WITH THE DUCT IN HIS LAP, GRASPING THE DUCT ANGLE IRON FLANGE WITH HIS HANDS. THIS EMPLOYEE WAS ELECTROCUTED. THE EMPLOYEE ON THE SCAFFOLD RECEIVED AN ELECTRIC SHOCK WHEN HE TOUCHED THE DUCT (THOUGH FOR SOME REASON HE WAS NOT LISTED ON THE OSHA 170 FORM AS BEING INJURED). HE WAS ABLE TO RELEASE THE DUCT AND CLIMB DOWN FROM THE SCAFFOLD. THE PLANT MAINTENANCE ELECTRICIANS MEASURED 120 VOLTS BETWEEN THE DUCT AND GROUND BEFORE RETRIEVING THE DEAD EMPLOYEE.

Keywords: CABLE TRAY, DUCT, E GI III, ELECTRICAL, ELECTROCUTED

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 100585256 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close