Accident Report Detail
Accident Summary Nr: 741322 - TWO EMPLOYEES INJURED WHEN SPRAYED BY HOT WATER AND CHEMICAL
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 112227327 | 08/23/1991 | 8062 | 0 | Kaiser Permanente |
Abstract: ON THE MORNING OF AUGUST 1, 1991, TWO INJURY ACCIDENTS OCCURRED INSIDE A HOSPITAL CENTRAL UTILITY PLANT. EMPLOYEE #1 WAS INJURED AT 9:50 A.M. WHEN THE CAP ON A PARTIALLY PRESSURIZED 5-GALLON POT FEEDER TANK FLEW OFF AND THE EMPLOYEE WAS SPRAYED WITH HOT WATER AND ANTI-CORROSIVE CHEMICALS FROM THE TANK, WHICH IS PART OF THE DOMESTIC HOT WATER SYSTEM. HE HAD JUST SERVICED THE TANK (ADDED CHEMICALS) AND TAPPED THE TWIST-ON CAP TO STOP A SMALL LEAK. THE CAP REACHED A SECOND RELEASE POINT AND FLEW OFF UNDER PRESSURE. THE SYSTEM HAD NO TURN LIMITING DEVICE FOR THE CAP, SUCH AS A STOP PIN. AT 11:20 AM., EMPLOYEE #2 SUFFERED SIMILAR INJURIES WHEN THE SAME CAP FLEW OFF AS HE TAPPED IT TO TRY TO STOP THE LEAK AFTER MAKING SOME ADJUSTMENTS TO THE CAP SEAL (GASKET).
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 112227327 | Hospitalized injury | Burn/Scald(Heat) | Miscellaneous plant and system operators | ||
| 2 | 112227327 | Non Hospitalized injury | Burn/Scald(Heat) | Miscellaneous plant and system operators |
Translate