Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 665703 - BURN - ELECTRICAL FAULT IN ELECTRICAL BOX

Accident Summary Nr: 665703 -- Report ID: 0112000 -- Event Date: 10/28/1997
Inspection NrDate OpenedSICNAICSEstablishment Name
12320349910/28/199730890Wiremold Company, Inc.

Abstract: Two plant electricians were installing a power load monitor for an energized 480-volt circuit breaker. The circuit breaker supplied a busway for machines and equipment in the plant. Wearing rubber insulating gloves and safety glasses, employee #1 installed clamp-ons onto each phase conductor on the load side of the circuit breaker. He then tried to attach alligator clips to the three phase conductors on the supply side of the circuit breaker. However, he could not get the alligator clips to stay on the conductors. The two employees decided to separate two strands of each phase conductor, insert a No. 12 solid conductor between the strands, and attach the clips to the strands. They used an uninsulated, flathead, metal-shank screwdriver to do this. They successfully completed installing a clip on the first phase conductor. Employee #1 then started to spread two of the strands on the next phase conductor. As he inserted the screwdriver between the strands, the upper shank of the screwdriver contacted the frame of the circuit breaker enclosure, causing an electrical fault. Both employees received burns to their arms and faces from the ensuing electric arc and were hospitalized for their injuries.

Keywords: BURN, E GI II, ELECTRIC ARC, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTRICAL WORK, CIRCUIT BREAKER, ELECTRICAL FAULT, HAND TOOL

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 123203499 Hospitalized injury Burn/Scald(Heat) Electricians
2 123203499 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close