Accident Summary Nr: 608109 - Employees hospitalized after being exposed to ammonia

Accident Summary Nr: 608109 -- Report ID: 0418100 -- Event Date: 06/27/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
1834266706/27/199020150Tyson Foods

Abstract: Maintenance workers changed a seal on a votator. They pressurized the system to 60 psi to check for leaks, then opened a valve to bring a vacuum compressor on-line to lower the pressure to normal operating pressure. The compressor had been shut down and was causing internal pressure in the system to continue to build up. A safety valve vented anhydrous ammonia to the building's roof as the pressure exceeded 150 psi. Ventilation intakes on the building's roof spread the ammonia vapors throughout the entire building. All employees were evacuated as the maintenance workers brought the compressor on-line and eventually lowered the pressure to close the safety relief valve. Ammonia vapors settled into low areas around the building, overexposing nine employees. Four employees were kept overnight at the hospital. An additional employee was admitted the following day.

Keywords: MAINTENANCE, VENTILATION, ANHYDROUS AMMONIA, HIGH PRESSURE, VALVE, OVEREXPOSURE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 18342667 Hospitalized injury Asphyxia Occupation not reported
2 18342667 Hospitalized injury Asphyxia Occupation not reported
3 18342667 Hospitalized injury Asphyxia Occupation not reported
4 18342667 Hospitalized injury Asphyxia Occupation not reported
5 18342667 Non Hospitalized injury Asphyxia Occupation not reported
6 18342667 Non Hospitalized injury Asphyxia Occupation not reported
7 18342667 Non Hospitalized injury Asphyxia Occupation not reported
8 18342667 Non Hospitalized injury Asphyxia Occupation not reported
9 18342667 Hospitalized injury Asphyxia Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close