Accident Summary Nr: 515221 - STRUCK BY FLYING OBJECT - ELECTRIC SWITCH FAILURE

Accident Summary Nr: 515221 -- Report ID: 0625700 -- Event Date: 10/19/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
11041748210/23/199029920Cit-Con Oil Corporation

Abstract: On October 19, 1990, a petroleum products company was restoring power to substations at one of its plants following outages on October 16 and 17. Five electricians were sent to one of the substations to restore power there and to disconnect the generators that had been supplying power to essential plant operations. The circuit breaker to feeder A had been opened, but not the breaker for feeder B, which was not part of the plan at this time. Fuses had been installed for the switches on the A feeder; one switch had been closed, and the switch to the 13,000/480-volt transformers was being closed. One of the electricians, who was standing behind the others, closed a switch on the B feeder, and it failed. (The failure might have been caused by moisture or a low oil level in the switch.) A flying piece of metal from the exploding switch struck one of the electricians and killed him.

Keywords: ELECTRICAL, ELECTRIC SWITCH, E GI VII, EQUIPMENT FAILURE, SUBSTATION, ELEC UTILITY WORK, ELECTRICAL FAULT, FLYING OBJECT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 110417482 Fatality Concussion Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close