Accident Summary Nr: 202556346 - Employee Burns Forehead and Hands in Electric Arc

Accident Summary Nr: 202556346 -- Report ID: 0950631 -- Event Date: 01/28/2013
Inspection NrDate OpenedSICNAICSEstablishment Name
31553303402/21/20131731238210Red Hawk Fire & Security (Ca) Llc

Abstract: On January 28, 2013, Employee #1, with Red Hawk Fire & Security (Ca) LLC, was replacing an old fire alarm system with a new one in a 14 story building, with a coworker. Employee #1 and the coworker were searching the basement level to find a junction box containing wires to the system. Employee #1 looked at the schematics, and it appeared that the juncture box was in the fan room where Employee #1 located an unmarked junction box which was the same color and dimensions that held the wires on the other floors. This box (18 in. by 18 in.), however, turned out to be 480 volts. The coworker loosened four screws in the corners and was holding the screwdriver when he began to lift and to pull the cover away from the box. While doing this, the coworker tilted the cover and touched it inside the box. When the coworker did this, an arc flashed that threw both Employee #1 and the coworker back. Employee #1 sustained burn injuries to his face and hands. Employee #1 later learned there was no junction box holding the missing wires. The wires had been spliced and dropped in one of the pipes. Employee #1 instructed his coworker to open an unmarked box that should have been marked with voltage, amps and other identifying information. The coworker did not have electrical training. The coworker was a full-time permanent employee of the employer with no other contracts. Employee #1 was hospitalized.

Keywords: BURN, ELECTRIC ARC, ALARM, FOREHEAD, ELEC UTILITY WORK, UNTRAINED, HAND
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Commercial building Alteration or rehabilitation $500,000 to $1,000,000 14

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 315533034 Hospitalized injury Burn/Scald(Heat) Electrical and electronic technicians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.