Accident Summary Nr: 202545489 - Employee Receives Flash Burns Working on Electrical Panel

Accident Summary Nr: 202545489 -- Report ID: 0950641 -- Event Date: 04/10/2013
Inspection NrDate OpenedSICNAICSEstablishment Name
31486500705/08/20138222611210Laccd East Los Angeles College

Abstract: At approximately 1:30 p.m. on April 10, 2013, Employee #1, with Laccd East Los Angeles College, was connecting electric ovens in the chemistry building to a spare 50 to 70 amp circuit breaker. Employee #1's usual practice was to leave electrical power turned on in the building where electrical work was being conducted, and Employee #1 usually worked without personal protective equipment. Employee #1 considered his type of work to be work he performed on de- energized circuits, because Employee #1 always switched the individual breakers, upon which he worked, to the off position. Employee #1 switched off the main disconnecting circuit breaker supplying electrical power to the chemistry building (H8). Unfortunately, the main disconnecting circuit breaker in this building had been bypassed during electrical work by a sub-contractor two months prior to Employee #1's work in the H8 building on April 10, 2013. The disconnecting circuit breaker was not labeled as being removed from service. As a consequence, Employee #1 dropped the dead panel into the energized electrical panel. Employee #1 was not wearing any personal protective equipment at the time of the accident. Employee #1 was hospitalized, after sustaining serious electrical arc-flash burns requiring surgery.

Keywords: BURN, ELECTRIC ARC, PANEL, PPE, OVEN, ELECTRICAL WORK, CIRCUIT BREAKER, DISCONNECTING MEANS

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 314865007 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close