Accident Summary Nr: 202479580 - Stationary Engineer Scalded by Hot Water

Accident Summary Nr: 202479580 -- Report ID: 0950644 -- Event Date: 12/03/2013
Inspection NrDate OpenedSICNAICSEstablishment Name
12620050012/17/20138069622310City Of Hope National Medical Center

Abstract: At 1:30 p.m. on December 3, 2013, an employee was working as a stationary engineer for the City of Hope National Medical Center. The employer was a cancer research hospital. The employee had been employed by that employer since December 1989. He was working on the condensate return unit in the mechanical room of the CBG Building. The drain valve was kept open, and the employee checked the water level inside the tank by viewing the side glass. There was no visible meniscus on the side glass. The employee ensured that the condensate pump IC-14 was turned off. Then he closed the handle to stop the water from flowing into IC-14 from the tank. The employee electrically disconnected the IC-14 and removed bolts on the bottom of the pump housing. As soon as the employee lifted the motor and pump, hot condensate came out and scalded him on the face, neck, arms, torso and thigh. The temperature of condensate was 85 degrees Celsius (185 degrees Fahrenheit). The condensate unit was equipped with two condensate pumps - IC-9 and IC-14. IC-9 was in operation during the repair work. The employee was wearing long sleeve cotton shirts, leather work gloves, and steel toe boots. The accident was caused because a worker had previously repaired the condensate return pump without effectively preventing it from inadvertent movement or release of stored energy. The assistant safety officer of the City of Hope National Medical Center reported the incident to the DOSH West Covina District office at 7:00 p.m. on December 3, 2013.

Keywords: BURN, BOILER, HEALTH CARE FACILITY, TORSO, EQUIPMENT FAILURE, LOCKOUT, BACK, PUMP, PRESSURE RELEASE, HOT WATER

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 126200500 Hospitalized injury Burn/Scald(Heat) Stationary engineers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close