Accident Summary Nr: 202444840 - Firefighter Is Injured During Hose Pressure Test

Accident Summary Nr: 202444840 -- Report ID: 0950633 -- Event Date: 11/03/2006
Inspection NrDate OpenedSICNAICSEstablishment Name
12588163111/29/20069224922160Chino Valley Independent Fire District

Abstract: On November 3, 2006, Employee #1 a fire fighter/paramedic with the Chino Valley Independent Fire District, was the designated pump operator during the performance of an annual hose test. The pump on the fire department apparatus was utilized to perform the test. Near the conclusion of the 5 minute, 400 psi test, while Employee #1 was reducing the pressure in a hose being tested, it failed near the pump discharge connection. The elbow connected to the discharge flew into his face. He was hospitalized at LLUMC for fractures. The hose service test involved a 900-ft-long layout of 4 in. hose sections. Each section measured 50 ft in length. Some sections had the acceptance test pressure stenciled on them with the phrase "Tested to 600 PSI". Other, newer sections had the service test pressure stenciled on them with the phrase "Service Test to 300 PSI". The hose section that failed was manufactured in January 1975 by American Rubber MFG and it was labeled "Tested to 600 PSI". The investigation revealed that the pressure test was not conducted in accordance with the NFPA 1962 provisions for pressure, length of hose tested simultaneously, and securing of the hose at the discharge.

Keywords: FIREFIGHTER, FRACTURE, HOSE, FLYING OBJECT, FACE, FIRE TRUCK, PRESSURE RELEASE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 125881631 Hospitalized injury Fracture Firefighting occupations

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close