Accident Summary Nr: 202342143 - Lineman Electrocuted Replacing Utility Pole

Accident Summary Nr: 202342143 -- Report ID: 0215000 -- Event Date: 06/21/2008
Inspection NrDate OpenedSICNAICSEstablishment Name
31224786906/23/20084931221122Eastern Construction & Electric, Inc.

Abstract: On June 21, 2008, Employee # 1 and Employee #2, electricians, were preparing to change out high-voltage electrical lines on a utility pole. A new utility pole was placed beside the old pole so that the existing high-voltage lines could be attached. Earlier in the day, Employee #1 and Employee #2 cut power to the electric lines leading to the utility pole that was to be worked on. At around 10:30 a.m., Employee #1 was elevating himself in an aerial lift when his shoulder came in contact with an electric line. Employee #2 brought Employee #1 to the ground and administered CPR. Employee #1 did not respond and had been electrocuted. Neither Employee #1 nor #2 performed any testing prior to approaching the high-voltage electric lines. The electricians failed to disconnect all of the jumpers at the pole down the line from the one they were preparing to work on. A jumper crossed from one side of the pole to the other to electrically connect the lines. A single jumper remained connected, which left one of the lines energized. Employee #1 came in contact with that line.

Keywords: OVERHEAD POWER LINE, POWER LINE WORKER, ELECTRICIAN, ELECTROCUTED, STRUCK AGAINST, ELECTRIC SHOCK, UTILITY POLE, AERIAL LIFT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 312247869 Fatality Electric Shock Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close