Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 202339370 - Employee burned by arc blast replacing defective breaker

Accident Summary Nr: 202339370 -- Report ID: 0352430 -- Event Date: 01/23/2002
Inspection NrDate OpenedSICNAICSEstablishment Name
30494210502/04/200217310Scott Power And Light

Abstract: On January 23, 2002, Employee #1, an electrician, and a coworker-helper were tasked with removing and replacing a defective emergency generator transfer switch for an elevator in a nursing home. Due to the age of the equipment, the switch had to be replaced. In order to maintain power to the building utilization equipment, it was necessary to reroute some of the wiring to the boiler room. The breaker to the switch was turned off, and the operation was completed. At this time, the generator needed to be reset to supply power to the boiler. Apparently a group of bunched "buck tailed" wires had shorted, tripping the breaker. A building engineer, who was in the boiler room, heard a "boom". The breaker had been damaged by the short, and Employee #1 and his helper went to their employer's shop to obtain another amplifier breaker. Upon returning to the nursing home, Employee #1 began removing the nine nuts holding the defective breaker in place when an arc blast occurred. He suffered first-, second-, and third-degree burns on his face, neck, chest, arms, and hands. During subsequent interviews, Employee #1 acknowledged that the panel had not been deenergized prior to starting the work. (It was reported that the panel could have been deenergized at a later time, but not at the time that the work was being performed.) He also stated that he and his employer had worked on jobs where the equipment had been de-energized or locked out. Causal factors of this accident include the employer's failure to ensure that lockout and tagout procedures were used, and the employer's failure to provide and ensure the use of appropriate PPE. The employer also did not have a written procedure in place.

Keywords: BURN, ELEC PROTECT EQUIP, ELECTRIC ARC, REPAIR, WORK RULES, CONSTRUCTION, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL FAULT, FACE
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Other building Maintenance or repair $500,000 to $1,000,000 6

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 304942105 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close