Accident Report Detail

Accident Summary Nr: 201798923 - Employee Is Burned in Electrical Accident

Accident Summary Nr: 201798923 -- Report ID: 0950644 -- Event Date: 07/01/2004
Inspection NrDate OpenedSICNAICSEstablishment Name
30133267207/08/20044911221122Southern Calif Edison

Abstract: A power line worker and his helper were troubleshooting a power outage. After diagnosing the problem as a burned-out fuse in a switch in an underground vault, the power line worker entered the vault to replace the fuse. He opened the cover on the switch; and, as he was replacing the fuse, an electrical fault occurred. The ensuing electric arc burned the employee. The employee used an access ladder to exit the 3.7-meter-deep vault before being transported to a hospital. He was hospitalized for 7 days with second- and third-degree burns to his face and arms. The worker had about 20 years' experience as a troubleman. He had been wearing gloves, Nomex clothing, and eye protection at the time of the accident. Another crew that had worked in the vault that same day had reversed the load-side and line-side cables.

Keywords: BURN, FUSE, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, PPE, E PTD, UNDRGRD INSTALLATION, ELEC UTILITY WORK, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 301332672 Hospitalized injury Burn/Scald(Heat) Misc. electrical & electronic equipment repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close