Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 201486107 - Employee killed in chemical explosion

Accident Summary Nr: 201486107 -- Report ID: 0950627 -- Event Date: 09/12/2003
Inspection NrDate OpenedSICNAICSEstablishment Name
12034049209/16/20031711238220Jenson Mechanical, Inc.

Abstract: At approximately 11:15 a.m. on September 12, 2003, Employee #1, a mechanic, was working in a propellant mix building owned by a different employer that made solid fuel rockets and missiles for the aerospace and defense industries. He was using a portable band saw to cut into a stainless-steel, 2 in. thick vacuum line designed to pull air from the rocket fuel being mixed. Employee #1 had partially cut the line when it exploded and he was killed. Subsequent investigation revealed that the inside of the line was contaminated with particles of HMX explosive and ammonium perchlorate, the latter having a particle size of less than 15 microns. The employer that owned the building failed to ensure that the line had been decontaminated of all explosive materials before Employee #1 began hot work.

Keywords: PORTABLE POWER TOOL, HEAT, BANDSAW, EXPLOSIVE MIXING, CONSTRUCTION, EXPLOSION, CHEMICAL REACTION, COMBUSTIBLE DUST, CHEMICAL
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Manufacturing plant Maintenance or repair $500,000 to $1,000,000 2 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 120340492 Fatality Other Occupation not reported Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Interior plumbing, ducting, electrical work
Fatality Cause: Fire/explosion

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close