Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 201320116 - electric shock - direct contact with energized parts

Accident Summary Nr: 201320116 -- Report ID: 0317900 -- Event Date: 10/20/1998
Inspection NrDate OpenedSICNAICSEstablishment Name
30232694710/21/199817310Carr & Duff, Inc.

Abstract: Two employees, an electrician and a helper, were repairing a damaged transformer and refusing and cleaning a Penn switch box (Model No. IS-S, Serial No. 13- 229-K) to restore power to a transformer manufacturing plant. The box had a Kirk interlock on the outside access door and enclosed a Kearney Iso Quencher gang switch. The electrician was standing directly in front of the open switch box door. He bent down and reached into the box to clean the inside contacts. He was electrocuted when his hand contacted the energized center contact of the three-phase switch. There was a malfunction in the Kearney switch, which was a problem known to the employer and other employees. The electrician had not been wearing his rubber insulating gloves and had not tested the circuit to ensure that it was deenergized before reaching into the box.

Keywords: ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, ELECTRIC SWITCH, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, INTERLOCK, LOCKOUT, ELEC CIRC PART--MISC
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Manufacturing plant Maintenance or repair Under $50,000 12 12 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 302326947 Fatality Electric Shock Electricians Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Other Activities-Installing Ornamental And Archite
Fatality Cause: Electric shock, other and unknown cause

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close