Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 201200565 - Electric Shock - Contact with Overhead Line thru Boom

Accident Summary Nr: 201200565 -- Report ID: 1054114 -- Event Date: 03/31/1999
Inspection NrDate OpenedSICNAICSEstablishment Name
30272368903/31/199917710Robert L Hoerauf Concrete Inc

Abstract: A concrete pump was being used to pour concrete into forms at a jobsite. The boom of the concrete pump contacted a 12-kilovolt overhead power line, and the employee who was directing the discharge tube from the pump received an electric shock. He was hospitalized for his injuries.

Keywords: CONCRETE PUMP, OVERHEAD POWER LINE, ELECTRICAL, BOOM, CONCRETE TRUCK, E C, ELECTRIC SHOCK
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Contractor's yard/facility New project or new addition Under $50,000

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 302723689 Hospitalized injury Electric Shock Concrete and terrazzo finishers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close