Accident Summary Nr: 201181625 - Employee injured while repairing steam pipe

Accident Summary Nr: 201181625 -- Report ID: 0950611 -- Event Date: 04/09/2003
Inspection NrDate OpenedSICNAICSEstablishment Name
30089269204/10/20038221611310Sf State University, Student Health Service

Abstract: At 12:00 noon on April 9, 2003, Employee #1 was repairing a pressurized steam line pipe in the mechanical room of Thornton Hall, in an attempt to stop a water leak in the lobby, when he was seriously injured by a sudden release of hot steam. At the time of accident, Employee #1 had started opening a 2-inch pipe union on the condensate receiver outlet, when the pressurized steam was suddenly released and burned Employee #1. The condensate steam pipe system was not isolated and blocked at the inlet and outlet to the steam trap in the hall ceiling. The valves were not secured and shut-off to prevent and stop immediately the condensate steam backing up into the steam trap. Workers secured only the main condensate valves nearer the trap rather than in the hall ceiling. The trap was not placed in a drip leg, but instead, it was connected directly into the steam line. Furthermore, this was a 15 psi steam trap installed in an 80 to 100 psi steam line which, more likely than not, would make the trap fail. No tags were used at the time of accident. Employee #1 sustained burns to his upper torso, neck, left cheek and nose. He was taken to Kaiser Hospital for further medical treatment and then moved to St. Francis Hospital. He was kept there for observation and was released on April 13, 2003.

Keywords: BURN, NOSE, TORSO, STEAM, NECK, PLUMBING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 300892692 Hospitalized injury Burn/Scald(Heat) Plumbers, pipefitters and steamfitters

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close