Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 201171451 - Fire extinguisher explodes injuring employee

Accident Summary Nr: 201171451 -- Report ID: 0950621 -- Event Date: 10/03/2001
Inspection NrDate OpenedSICNAICSEstablishment Name
12578232610/19/200173890Solon Fire Protection

Abstract: At 11:30 a.m. on October 3, 2001 Employee #1 had recently attempted to do servicing of the regulator he was using to pressurize a fire extinguisher. In the reassembly of the regulator, Employee #1 had inadvertently bypassed the regulating diaphragm. As a result of this action, a pressure of 2500 lbs. of nitrogen was instantly put into the fire extinguisher. The extinguisher was designed for only 150 lbs. of propellant pressure. The fire extinguisher blew apart and Employee #1 suffered severe lacerations and a chest injury. He was hospitalized for three days.

Keywords: FIRE EXTINGUISHER, FIRE, EXPLOSION, PRESSURE RELEASE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 125782326 Hospitalized injury Other Technicians, n.e.c.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.