Return to Accident Search Results
Accident Report Detail
Accident Summary Nr: 201063716 - Burn - Electrical Fault in Electrical Cabinet
Accident Summary Nr: 201063716 -- Report ID: 0950632 -- Event Date: 04/05/2001
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
| 120275177 | 04/11/2001 | 1731 | 0 | Sadler Electric Inc |
Abstract:
An electrician was installing a temporary circuit breaker for an elevator. He was installing the circuit breaker in an energized panelboard. (The general contractor required the distribution panelboard to remain energized because the building was occupied.) As the electrician, who was not wearing rubber insulating gloves, was using a razor knife to cut the electrical tape on a 480-volt bus, he caused an electrical fault. The ensuing electric arc burned the employee. He was hospitalized for 7 days with second-degree burns on his face and right two fingers. The electrician had been trained and had 4 years of experience.
Keywords:
BURN, ELECTRIC ARC, ELECTRICAL, BUSBAR, ELECTRICAL WORK, LOCKOUT, E C, ELECTRICAL CABINET, ELECTRICAL FAULT
Accident Details
| End Use |
Project Type |
Project Cost |
Stories |
Non-building Height |
Fatality |
| Other building |
Maintenance or repair |
Under $50,000 |
|
|
|
Employee Details
| Employee # |
Inspection Nr |
Age |
Sex |
Degree of Injury |
Nature of Injury |
Occupation |
| 1 |
120275177 |
|
|
Hospitalized injury |
Burn(Chemical) |
Electricians |