Accident Summary Nr: 201034139 - Two employees burned when hot water return pipe burst

Accident Summary Nr: 201034139 -- Report ID: 0950635 -- Event Date: 12/27/2001
Inspection NrDate OpenedSICNAICSEstablishment Name
30076285312/27/200117110Advanced Mechanical Contractors

Abstract: On December 27, 2001, two employees suffered severe thermal burns when the hot water return pipe that they were removing suddenly released 180-degree water. There were four employers involved in this accident: the site employer; the HVAC contractor hired by the site employer to run site employer's HVAC needs; Employee #1, the plumber who was conducting the major plumbing repairs for the site employer; and Employee #2, the backhoe operator, who was contracted by the plumbing contractor to do the digging. Employee #1 was in the process of grinding off the bolts on a flange which connected the 8-inch fiberglass main line to the 4-inch-diameter, 4-foot-high standpipe he was removing. The standpipe was leaking hot water 8 feet underground. The HVAC contractor, who controlled the site, had isolated the segment being worked on by closing the two gate valves at each end of the segment. After some time, sensing that the system had been bled empty, since no water was observed coming out of the drain valve, the HVAC contractor closed the drain valve. Immediately after he closed the drain valve, a six inch strip of the valve seating liner broke and caused water to leak into the isolated, closed pipe. The water, entering the isolated segment at about 70 pounds per square inch, built pressure and caused air and water to release suddenly out of the standpipe which was being removed, some 1,200 feet away. The sudden release of water scalded Employee #1, who was inside the excavation as the water rose approximately 8 to 12 feet into the air for several seconds. Employee #1 was experiencing difficulty exiting the hole because steam had built up inside the excavation. Employee #2, who was watching the plumber, was also burned by the sudden release of hot water because he was sitting on the edge of the excavation and because he assisted Employee #1 up the ladder. Both Employee #1 and Employee #2 were hospitalized for treatment of their burns.

Keywords: BURN, TORSO, TRENCH, PLUMBING, ARM, ACCIDENTAL DISCHARGE, BACKHOE, HOT WATER
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Pipeline Maintenance or repair Under $50,000 8

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 300762853 Hospitalized injury Burn/Scald(Heat) Occupation not reported Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause:
Fatality Cause:
2 300762853 Hospitalized injury Burn/Scald(Heat) Plumbers, pipefitters and steamfitters Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Trenching, installing pipe
Fatality Cause: Other

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.