Accident Summary Nr: 200961795 - ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

Accident Summary Nr: 200961795 -- Report ID: 0352420 -- Event Date: 10/28/1997
Inspection NrDate OpenedSICNAICSEstablishment Name
30069367810/29/199716230Henkels & Mccoy, Inc.

Abstract: Two power line workers were standing in a crane-suspended personnel platform being hoisted by a truck crane. They were going to attach a grounding cable to a static line for an overhead power line. After that, they were going to install a block for pulling in a new fiber-optic cable. While the personnel platform was being hoisted, high winds blew the platform toward the deenergized power line. One of the employees reached out, touched the power line, and received an electric shock. The platform continued toward the line, and the employee contacted it a second time. His coworker saw that the injured employee was in trouble, so he signaled the crane operator to lower the platform. The injured employee was not breathing, so his coworkers administered cardio-pulmonary resuscitation to no avail. The injured employee was transported to a hospital, where he was pronounced dead. Although the power line was deenergized, a nearby line had induced voltage on it. Neither of the employees was using electrical protective equipment at the time of the accident.

Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK, WORK PLATFORM, CRANE
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Powerline, transmission line Alteration or rehabilitation $50,000 to $250,000 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 300693678 Fatality Electric Shock Electrical power installers and repairers Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Installing interior walls, ceilings, doors
Fatality Cause: Electrocution by touching exposed wire/source

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.