Accident: 200850519 - Employee Killed When Crushed By Elevator Car

Accident: 200850519 -- Report ID: 0215000 -- Event Date: 11/17/1997
InspectionOpen DateSICEstablishment Name
10989332111/17/19977699Millar Elevator Industries Inc.

Employee #1, an elevator mechanic, was working on the switches in an elevator that were malfunctioning in various ways. The in-the-car and top-of-car operating devices were not working correctly. The UP button worked on top of the car and the DOWN button worked in the car, but not vice versa. In addition, the switch that engaged the top-of-car device did not lock out all the in-the-car switches, as it should have. Employee #1 defeated the deadman key switch in the elevator by using a piece of wood to keep positive pressure on it. As shown on the surveillance video displays, Employee #1 was lying on the floor halfway in and halfway out of the elevator when it moved down, crushing him between the fourth floor landing and the elevator ceiling. He was killed. It is believed that Employee #1 had unintentionally pressed the DOWN button in the elevator, which should have been locked out had the switch on top of the car been functioning correctly. He was working alone at the time of the accident.

Keywords: deadman control, work rules, mechanic, descending, caught between, crushed, elevator, mech malfunction

Employee Details
Employee # Inspection Age Sex Degree Nature Occupation
1 109893321 Fatality Other Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close