Accident Summary Nr: 200841120 - Employee electrocuted while changing lighting ballasts

Accident Summary Nr: 200841120 -- Report ID: 0524530 -- Event Date: 08/02/2005
Inspection NrDate OpenedSICNAICSEstablishment Name
30382218308/02/20051731238210Lowry Electric Company
Inspection NrDate OpenedSICNAICSEstablishment Name
30382219108/02/20054939221122Illinois Power Company Dba Amerenip

Abstract: At approximately 1:35 p.m. on August 2, 2005, Employee #1, a journeyman electrician, had been working alone for about an hour on a time and material job in the garage/shop area of an office facility. He was changing bulbs and ballasts on a branch circuit of nine 8 ft long fluorescent luminaries energized at 277 volts. He was changing a Universal Lighting Technologies ballast, model 937KTCP, when he contacted an energized 16-gauge line conductor and was electrocuted. At approximately 1:40 p.m., a mechanic discovered Employee #1 slumped over in the elevated scissor lift. He ran across the garage/shop, turned off the single pole switch, and sought assistance. Several people who were either working nearby or happened upon the scene during the 2:00 p.m. shift change, helped coordinate the emergency response, retrieve Employee #1 from the lift, and render first aid/CPR. He had electrical burns on both hands and the front of his chest. Employee #1 was transported to the hospital, where he was pronounced dead. The line conductor that shocked him was fitted with a 5-amp in-line fuse that had not been removed or disconnected. Both the breaker at a Westinghouse NHIB-3P/4W panel board and a single pole switch were activated. Employee #1 was not wearing gloves rated for the voltage involved. In addition, he was working from an uninsulated, manually propelled 115-volt Pac Craft electric scissor lift, model 125 EM, plugged into a GFCI receptacle, which provided the potential difference, path to ground.

Keywords: LIGHTING CIRCUIT, WORK RULES, AERIAL LIFT, ELEC PROTECT EQUIP, ELECTRICIAN, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, ELEC CIRC PART--MISC
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Commercial building Maintenance or repair Under $50,000 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation Construction
1 303822183 Fatality Electric Shock Electricians Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause: Interior plumbing, ducting, electrical work
Fatality Cause: Electrocution by touching exposed wire/source
2 303822191 Occupation not reported Distance of Fall: feet
Worker Height Above Ground/Floor: feet
Cause:
Fatality Cause:

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.