Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 200758571 - Employee electrocuted by contact with overhead conductor

Accident Summary Nr: 200758571 -- Report ID: 0522500 -- Event Date: 12/03/2007
Inspection NrDate OpenedSICNAICSEstablishment Name
31048274012/04/20071731238210New River Electrical Corporation

Abstract: On December 1, 2007, Employee #1 and a coworker, of the New River Electrical Corporation, were using a JLG aerial lift to install new electrical equipment. At the time of the accident, they were removing the ground from a 345-kilovolt electrical line. The coworker was holding the hot stick and, once the JLG basket had been raised and positioned between two overhead conductors, he began to remove the ground. Employee #1 was reaching over to assist him when he contacted an overhead conductor and was electrocuted. The coworker holding the hot stick felt a tingle, but he was not injured. The area the employees were working in was very congested and too small for the lift they were using. This caused them to violate the minimum approach distance. The line was de-energized, however induced voltage was still present. A secondary ground had not been installed to protect the employees from induced voltage. The employees were not familiar with working with high voltage and were not clear on the hazards of induced voltage. The workers in the JLG lift were fourth- and fifth-step apprentices. The assigned foreman for the site, a seventh-step apprentice, had left the site temporarily to obtain fuel and there was no other supervision available to observe the job task.

Keywords: CLEARANCE, OVERHEAD POWER LINE, ELECTRICAL, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, INEXPERIENCE, INDUCED CURRENT, AERIAL LIFT
Accident Details
End Use Project Type Project Cost Stories Non-building Height Fatality
Powerplant New project or new addition $5,000,000 to $20,000,000 1 40 X

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 310482740 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close