Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 200540730 - Employee is asphyxiated in gas pipe line

Accident Summary Nr: 200540730 -- Report ID: 0317500 -- Event Date: 02/08/2002
Inspection NrDate OpenedSICNAICSEstablishment Name
30418618202/11/200226210Appleton Papers Incorporated

Abstract: Employee #1 entered a gas pipeline for a maintenance operation. He was overcome by gas in the pipe and died of asphyxia.

Keywords: MAINTENANCE, ASPHYXIATED, VAPOR, CONFINED SPACE, GAS, PIPELINE, PURGING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 304186182 Hospitalized injury Asphyxia Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close