Accident Summary Nr: 170824445 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

Accident Summary Nr: 170824445 -- Report ID: 0352440 -- Event Date: 06/13/1996
Inspection NrDate OpenedSICNAICSEstablishment Name
12737399106/14/199617310Bausum & Duckett Electric Company, Inc.

Abstract: An electrician had pulled some conductors from a junction box to inspect them. After the electrician finished the inspection, an apprentice electrician put the 277-volt conductors back into the box. The No. 12 AWG conductors were spliced with red Ideal wire nuts designed for use with conductors sized from No. 10 to 18 AWG. The electrician had failed to notice during the inspection that one of the ungrounded circuit conductors was stripped back about 3 millimeters past the end of the wire nut. The apprentice contacted the bare portion of the conductor as he was pushing the energized conductors back into the box. (The circuit was energized to provide lighting for the working office area.) He received an electric shock and was hospitalized for his injury.

Keywords: E GI II, ELEC INSULATION, LIGHTING CIRCUIT, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, ELECTRICAL BOX

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 127373991 Hospitalized injury Electric Shock Electricians' apprentices

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close