Accident Summary Nr: 170751325 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 170751325 -- Report ID: 0352440 -- Event Date: 04/20/1992
Inspection NrDate OpenedSICNAICSEstablishment Name
11951445304/21/199217990Consolidated Equipment Erectors, Inc.

Abstract: A WORKER OF A CONSTRUCTION CONTRACTOR AND AN EMPLOYEE OF A SOFT DRINK BOTTLING COMPANY WERE WORKING TOGETHER. THE CONTRACTOR HAD BEEN HIRED TO REMOVE EQUIPMENT, AND THE TWO EMPLOYEES WERE CLEANING UP AND REMOVING CONDUCTORS FROM CONDUITS LOCATED IN THE BUILDING'S CONCRETE FLOOR. THE CONSTRUCTION WORKER WAS HAVING SOME DIFFICULTY REMOVING A CONDUCTOR FROM A WATER TREATMENT ROOM. HE TOLD HIS COWORKER THAT HE WAS GOING TO CHECK THE ELECTRIC POWER SUPPLY ROOM TO SEE WHY THE CONDUCTOR WAS STUCK. THE COWORKER TOLD HIM NOT TO WORRY ABOUT IT, BUT THE CONSTRUCTION WORKER WENT INTO THE ELECTRICAL ROOM ANYWAY. THE TWO EMPLOYEES, WHO WERE NOT ELECTRICIANS, HAD NOT RECEIVED TRAINING IN ELECTRICAL HAZARDS. THE DOOR TO THE ELECTRIC POWER SUPPLY ROOM WAS MARKED, "DANGER, HAZARD OF ELECTRIC SHOCK OR BURN, TURN OFF POWER SUPPLYING THIS EQUIPMENT BEFORE WORKING ON OR INSIDE". THIS ROOM SUPPLIED ELECTRIC POWER TO THE ENTIRE SITE. ONCE INSIDE, THE CONSTRUCTION EMPLOYEE WENT OVER TO A SWITCHBOARD. THE SWITCHBOARD, WHICH CONTAINED THE SAME WARNING AS THE DOOR TO THE ROOM, WAS A SQUARE D SERIES 3 POWER STYLE SWITCHBOARD RATED AT 1600 AMPERES, 480/277 VOLTS, THREE PHASE, FOUR WIRE. CIRCUIT BREAKERS NUMBERED 2 THROUGH 5 WERE IN THE OFF POSITION; THE REMAINING BREAKER (NUMBER 1) WAS IN THE CLOSED POSITION. THE CONSTRUCTION WORKER OPENED THE DOOR ON THE SWITCHBOARD AND CONTACTED AN ENERGIZED BUSBAR. HIS COWORKER FOLLOWED HIM IN AND SAW HIM IN DISTRESS. THE COWORKER PULLED HIM AWAY BY HIS WAIST BAND. PARAMEDICS ARRIVED WITHIN 3 MINUTES AND TRANSPORTED THE INJURED EMPLOYEE TO THE HOSPITAL. HOWEVER, THE CONSTRUCTION WORKER DIED OF ELECTROCUTION.

Keywords: E GI III, ELECTRICAL, SWITCHBOARD, ELECTROCUTED, LOCKOUT, UNTRAINED

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119514453 Fatality Electric Shock Construction trades, n.e.c.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close