Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170751176 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

Accident Summary Nr: 170751176 -- Report ID: 0352450 -- Event Date: 07/12/1995
Inspection NrDate OpenedSICNAICSEstablishment Name
11960480907/13/199517910Commercial Erectors, Incorporated

Abstract: A painter was painting from a 30-ton overhead crane (Model No. 30TON KDBET, Serial No. 4302). The overhead crane was designed with a platform from which employees could work while operating the crane. Although fall protection was needed while an employee was working from the crane platform, the employee was not wearing personal fall arrest equipment. He left the work platform and accessed the I-beam trolley track of another overhead crane. He reached over the track and contacted a 277-volt runway conductor for the crane. He received an electric shock, which knocked him off the structure. He fell 10 feet, 3 inches, struck his head on the corner of the crane's lifting hatch, and fell through the hatch 42 feet, 2 inches to the first floor. He died from his injuries. Investigation revealed that the employee had been trained in and provided with fall protection; however, he had been working without supervision. No worksite inspection had been conducted, and the employee had not been trained in electrical safety-related work practices related to working around crane runway conductors. (The company had a two-page, written safety program consisting of 19 work rules.) The employee had been provided with only 0.5 foot-candles of illumination while he was working from the crane and the track.

Keywords: E GI III, ELECTRICAL, RUNWAY CONDUCTOR, LOCKOUT, OVERHEAD CRANE, ELECTRIC SHOCK, FALL, FALL PROTECTION

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119604809 Fatality Electric Shock Painters, construction and maintenance

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close