Accident Summary Nr: 170566772 - CARBON MONOXIDE POISONING

Accident Summary Nr: 170566772 -- Report ID: 0552700 -- Event Date: 01/17/1997
Inspection NrDate OpenedSICNAICSEstablishment Name
30036411401/21/199758120Rosengren & Associates, Inc Dba Sunshine Factory

Abstract: After his shift was over at 3:30 PM on January 17, 1997, a preparation cook supervisor for a restaurant apparently spent sometime in the bar and then went to the mechanical room to sleep. The 3.0-meter by 3.4-meter room was located in a corner of the basement and contained two gas water heaters. On January 19, 1997, at 12:30 AM, the employee was found dead in the mechanical room. He had died of carbon monoxide poisoning. One water heater had malfunctioned and was producing excessive carbon monoxide. The duct at the wall connection to the outside exhaust was corroded through. The fire department and gas utility measured carbon monoxide at 800 parts per million with the room closed after water heaters had been running for 20 to 30 minutes with a constant flow of water. They measured carbon monoxide at 8000 parts per million in the heater's flue gas.

Keywords: EXHAUST SYSTEM, LEAK, NATURAL GAS, EXHAUST FUMES, POISONING, WATER HEATER, CARBON MONOXIDE, MECH MALFUNCTION

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 300364114 Fatality Asphyxia Supervisors, food preparation & service occupation

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close