Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170340590 - BURN - ELECTRICAL FAULT IN PANELBOARD

Accident Summary Nr: 170340590 -- Report ID: 0317900 -- Event Date: 03/10/1993
Inspection NrDate OpenedSICNAICSEstablishment Name
1787272203/10/199365310Willner Properties

Abstract: AN EMPLOYEE HAD REMOVED THE COVER TO AN ITE 1200-AMPERE MAIN CIRCUIT PANELBOARD TO TEST VOLTAGES. THE TESTING WAS PERFORMED IN RESPONSE TO A REPORT THAT THERE WAS A POWER FLUCTUATION AFFECTING THE BUILDING. THE ELECTRIC UTILITY WANTED TO WAIT UNTIL THE FOLLOWING DAY TO RUN TESTS ON THE SERVICE, SO NO FURTHER WORK WAS DONE ON THE PANELBOARD, AND ITS COVER WAS REPLACED. WHEN THE COVER HAD FIRST BEEN REMOVED, SOME OF THE PLASTIC CIRCUIT BREAKER BLANKS HAD FALLEN OUT OF THE OPENINGS. WHEN HE INSTALLED THESE BLANKS BACK IN THEIR OPENINGS, THE EMPLOYEE USED THE BACK OF HIS FIST TO POUND ONE OF THE BLANKS TO MAKE IT FIT. ALUMINUM WIRING HAD BEEN USED IN THE ORIGINAL INSTALLATION TO THE MAIN BREAKER. APPARENTLY, THE CONDUCTOR ON THE RIGHT SIDE OF THE PANELBOARD CAME LOOSE IN ITS LUG, AND THE EMPLOYEE'S POUNDING CAUSED THE CONDUCTOR TO POP LOOSE AND CONTACT THE FRONT PANELBOARD COVER. THE ELECTRIC ARC FROM THE RESULTANT ELECTRICAL FAULT BLEW A HOLE IN THE COVER AND BURNED THE EMPLOYEE. THE SUPPLY FROM THE ELECTRIC UTILITY RECLOSED ON THE FAULT TWICE, AND THE EMPLOYEE RECEIVED BURNS FROM THREE SEPARATE ELECTRIC ARC BLASTS. THE EMPLOYEE WAS HOSPITALIZED WITH BURNS TO HIS FACE, ARMS, HANDS, AND RIGHT THIGH.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI III, ELECTRICAL, PANELBOARD, ELECTRICAL WORK, ELECTRIC CONDUCTOR, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 17872722 Hospitalized injury Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close