Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170204424 - BURN - ELECTRICAL FAULT IN PANELBOARD

Accident Summary Nr: 170204424 -- Report ID: 0950611 -- Event Date: 09/08/1994
Inspection NrDate OpenedSICNAICSEstablishment Name
11961489909/27/199417310Sierra Electric

Abstract: A journeyman electrician for an electrical contractor was replacing a circuit breaker in a panelboard. The panelboard was over 30 years old. The electrician, who had 8 years of experience, had performed this task thousands of times in the past. The bus in the panelboard was held by two screws: one at the top and one at the bottom. The employee unscrewed the bottom screw. Unfortunately, the top of the bus was loose, and it rotated against another bus when the bottom screw was loosened. The resulting electrical fault caused an electric arc, which burned the employee (who was not wearing any eye protection) on the face and hands. The employee spent 24 hours in intensive care at a hospital, before he was transferred to the trauma ward.

Keywords: BURN, E GI II, ELECTRIC ARC, ELECTRICAL, PPE, ELECTRICIAN, PANELBOARD, BUSBAR, ELECTRICAL WORK, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119614899 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.