Accident Summary Nr: 170155568 - ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC SCREWDRIVER

Accident Summary Nr: 170155568 -- Report ID: 0950645 -- Event Date: 12/06/1990
Inspection NrDate OpenedSICNAICSEstablishment Name
11221676712/06/199017420National Drywall
Inspection NrDate OpenedSICNAICSEstablishment Name
11221692412/06/199017420California Employee Management, Inc.

Abstract: An employee was hanging drywall in a tenant improvement construction project. He was working with a helper and his supervisor. The drywall installer was standing on the fourth step of a 2.4-meter-tall, Werner Class 1A, double-sided stepladder. The stepladder had four rubber feet. The helper was on the other side of the ladder, holding his Hilti Kwik Driver screwdriver (Serial No. 197338/KT). There was no electrical power in the work area, so the tool was connected by an extension cord set to a permanent outlet that was down the hall about 10 meters. The tool had a ground fault that energized its case. (The voltage was later measured to be 31.5 volts with the tool off.) The installer uttered "pipe" twice (in Spanish) and slumped over the top of the ladder, unconscious. He had been electrocuted. The employee's forehead had contacted an overhead condensate drainpipe, which provided a path to ground. The helper had been holding the screwdriver against the ladder, energizing it.

Keywords: ELECTRIC SCREW GUN, ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 112216767 Fatality Electric Shock Drywall installers
2 112216924 Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.