Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170097497 - BURN - ELECTRICAL FAULT IN MOTOR CONTROL CENTER

Accident Summary Nr: 170097497 -- Report ID: 1055360 -- Event Date: 03/08/1992
Inspection NrDate OpenedSICNAICSEstablishment Name
11121257703/10/199249110Washington Public Power Supply System

Abstract: An electric utility employee was using a paintbrush to dust a motor control center. The 50-millimeter-wide paintbrush had a metal band binding the bristles to its handle. To perform this job, the employee had opened the circuit breaker to the motor; however, the line side of the breaker was still energized. The opening between the line side of the circuit breaker and the grounded frame was about 38 millimeters wide. When the employee put the brush into this opening to dust inside, an electrical fault occurred. The ensuing electric arc and fire burned the employee's right hand, arm, and shoulder, and his face, back, and head. The burns ranged from first degree to third degree. The employee was hospitalized for his injuries.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI III, ELECTRICAL, FIRE, CIRCUIT BREAKER, ELEC UTILITY WORK, ELECTRICAL CABINET, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 111212577 Hospitalized injury Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close