Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 170080865 - Three employees burned to death in hydrocarbon fire

Accident Summary Nr: 170080865 -- Report ID: 0625700 -- Event Date: 08/02/1993
Inspection NrDate OpenedSICNAICSEstablishment Name
10763521108/02/199329110Exxon Company, Usa
Inspection NrDate OpenedSICNAICSEstablishment Name
10763520308/03/199329110Hall-Buck Marine, Inc.

Abstract: Employees #1 through #3 were working with drums A, B, C, D in a coker unit, which thermally cracks heavy residual feeds through a process called delayed coking. The employees were preparing to switch feed from the C drum to the D coke drum. This process involves opening and closing a number of valves. Employee #1 was on the 55 ft level where the switch valve was located. Employee #3 was also on the 55 ft level, approximately 50 ft away from Employee #1. Employee #2 was on the 40 ft level to prepare for the switch. Employee #1 told the controller over the radio to divert half of the feed flow to the D drum. At approximately the same time, they heard a noise and saw a vapor cloud rising from the vicinity of the feed pumps. The cloud ignited and fire went as high as the 141 ft level, fatally burning Employees #1, #2, and #3. Two other employees on the 40 ft level evacuated to safety. The leak was caused by a sudden failure of a 45 degree elbow in the 6 in. discharge line of the furnace feed pump(s).

Keywords: BURN, LEAK, FLAMMABLE VAPORS, DRUM, FIRE, COKE DRUM, ACCIDENTAL DISCHARGE

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 107635211 Fatality Burn/Scald(Heat) Occupation not reported
2 107635211 Fatality Burn/Scald(Heat) Occupation not reported
3 107635203 Fatality Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.