Accident Summary Nr: 170068084 - Employees injured when failed acid gas scrubber released gas

Accident Summary Nr: 170068084 -- Report ID: 0352450 -- Event Date: 03/04/1992
Inspection NrDate OpenedSICNAICSEstablishment Name
11960759603/06/199228790Fmc Corporation

Abstract: During batch production of bifenthrin, gases are normally released in the reactor vessel and are delivered by a closed system to an acid gas scrubber for neutralization with sodium hydroxide. This scrubber failed because the sodium hydroxide feed line clogged, releasing a plume that was probably a mixture of hydrochloric acid and sulfur dioxide gases. The plume was blown across the facility, including the chemical laboratory where technicians and supervisors were working. The chem lab's own HVAC system pulled some of the plume into the building, driving out the five technicians and one supervisor, who were choking, coughing, and having difficulty breathing. Two employees had been walking to a job site and had encountered the same plume. The plant nurse had been alerted and administered oxygen until the ambulances arrived and took Employees #1 through #8 to local hospitals. The employer had extensive written emergency response and evacuation procedures that are practiced six times a year, and designated employees are given emergency response training (emergency respirator use, confined space entry, acid spill containment) weekly. No violations were noted with procedures or responses.

Keywords: HYDROCHLORIC ACID, LUNG, SODIUM HYDROXIDE, ASPHYXIATED, VENTILATION, INHALATION, CLOGGED, SULFUR DIOXIDE, GAS LEAK, CHEMICAL VAPOR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 119607596 Hospitalized injury Asphyxia Occupation not reported
2 119607596 Hospitalized injury Asphyxia Occupation not reported
3 119607596 Hospitalized injury Asphyxia Occupation not reported
4 119607596 Hospitalized injury Asphyxia Occupation not reported
5 119607596 Hospitalized injury Asphyxia Occupation not reported
6 119607596 Hospitalized injury Asphyxia Occupation not reported
7 119607596 Hospitalized injury Asphyxia Occupation not reported
8 119607596 Hospitalized injury Asphyxia Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.