Accident Summary Nr: 14567606 - ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 14567606 -- Report ID: 0454510 -- Event Date: 07/23/1984
Inspection NrDate OpenedSICNAICSEstablishment Name
1513995908/01/198449110S C E & G
Inspection NrDate OpenedSICNAICSEstablishment Name
1513996708/01/198416290Crs Sirrine Services Inc
Inspection NrDate OpenedSICNAICSEstablishment Name
1514031208/01/198416290Becon Construction Inc

Abstract: A QUALITY CONTROL SUPERVISOR WAS CHECKING A SWITCHGEAR FOR FACTORY DEFECTS. THE SWITCHGEAR, WHICH HAD BEEN INSTALLED RECENTLY, WAS LOCATED IN THE MAIN SWITCHGEAR BUILDING. THE SWITCHGEAR WAS ENERGIZED AT 4800 VOLTS AND WAS RATED AT 2000 AMPERES. THE SUPERVISOR HAD NO TRAINING IN WORKING ON ENERGIZED CIRCUITS. HOWEVER, HE WANTED TO CHECK THE ELECTRICAL CONNECTIONS, AND HE THOUGHT THE CIRCUIT WAS DEENERGIZED. THE EMPLOYEE CAME INTO CONTACT WITH AN ENERGIZED PART AND RECEIVED SEVERE BURNS, WHICH CAUSED HIS DEATH. NO TEST EQUIPMENT WAS PRESENT TO DETERMINE IF THE CIRCUIT WAS DEENERGIZED (AS OUTLINED IN THE COMPANY'S PROCEDURES).

Keywords: ELECTRICAL, ELECTRIC SHOCK, BURN, LOCKOUT, E PTD, ELEC UTILITY WORK, SWITCHGEAR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 15139959 Fatality Electric Shock Electrical and electronic technicians
2 15139967 Occupation Not Listed
3 15140312 Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.