Accident Summary Nr: 14523369 - ELECTRIC SHOCK - FAULT IN DISTRIBUTION SWITCH

Accident Summary Nr: 14523369 -- Report ID: 0522300 -- Event Date: 08/20/1985
Inspection NrDate OpenedSICNAICSEstablishment Name
10006519208/21/198549110Ohio Edison Co Medina Line Shop

Abstract: AN EMPLOYEE WAS ASSIGNED TO OPEN A 69-KILOVOLT OVERHEAD POWER LINE BETWEEN TWO SUBSTATIONS. AS HE OPENED THE MANUAL SWITCH HANDLE AT THE BOTTOM OF THE POLE (GROUND LEVEL), A FAULT OCCURRED IN THE SWITCH AT THE TOP OF THE POLE. CURRENT PASSED THROUGH A #6A COPPER-CLAD METAL GROUND WIRE THAT WAS BONDED TO THE SWITCH HANDLE AT THE BOTTOM OF THE POLE. THE FAULT PASSED ENOUGH CURRENT TO ENERGIZE THE SWITCH HANDLE AND ELECTROCUTE THE EMPLOYEE.

Keywords: ELECTRICAL, ELECTRIC SWITCH, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 100065192 Fatality Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.