Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14496889 - ELECTRIC SHOCK - CONTACT WITH LIVE PART THRU CONDUCTOR

Accident Summary Nr: 14496889 -- Report ID: 0627100 -- Event Date: 05/01/1988
Inspection NrDate OpenedSICNAICSEstablishment Name
10678548805/02/198817310Cache Valley Electric

Abstract: A FOREMAN AND THREE OTHER EMPLOYEES WERE GROUNDING A FENCE SURROUNDING A SWITCHYARD. THE EQUIPMENT IN THE SUBSTATION WAS ENERGIZED WHILE THEY PERFORMED THEIR WORK. ONE OF THE EMPLOYEES HAD CUT NUMEROUS PIECES OF NO. 2 AWG SOLID COPPER CONDUCTOR INTO 8.5-FOOT LENGTHS. HE HAD BEEN DOING THIS BY LAYING THE CONDUCTOR ON THE GROUND, ROLLING OFF THE CONDUCTOR. HE THEN ROLLED THE CONDUCTOR OVER HIS HEAD, AND THE CONDUCTOR CONTACTED A 34.5-KILOVOLT TERMINAL THAT WAS ABOUT 9 FEET ABOVE THE GROUND. NONE OF THE OTHER EMPLOYEES WITNESSED THE ACCIDENT; HOWEVER, WHEN THEY HEARD THE ARC, THEY TURNED AROUND AND SAW THE INJURED EMPLOYEE FALLING BACKWARDS WITH THE COPPER CONDUCTOR IN HIS HAND. HE HAD BEEN ELECTROCUTED.

Keywords: ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 106785488 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.