Accident Summary Nr: 14482327 - ELECTRIC SHOCK - CONTACT WITH LIVE CONDUCTOR THRU TOOL

Accident Summary Nr: 14482327 -- Report ID: 0316400 -- Event Date: 08/19/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
76108008/21/198717110Power Maintenance Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
76107208/21/198717990Industrial Fire Proofing & Insulation Company
Inspection NrDate OpenedSICNAICSEstablishment Name
76106408/21/198717110Babcock & Wilcox Construction Company Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
76105608/19/198717310Pasquale Electric Co.

Abstract: A supervisor and two other employees entered a motor control center to inspect a boiler feed pump circuit to ensure that it was deenergized so that they could cut some cables that were part of the circuit. The three employees attached a come-along around a beam at the motor end of one of the cables. One of the employees (employee #2) left to get more chokers while the other two employees inspected the two sets of cables in the condenser pit area of the boiler. When he returned, employee #2 was told by his coworker that the supervisor had showed him the exact cables to cut. These two employees then went back to cut the cables. Employee #1 climbed down onto the lower cable tray that was supporting two sets of four cables coming through the wall. Employee #1 stated that he was told to cut the top left and bottom right cables. Using a pair of Klein ratchet-type wire cutters, he cut into a 2300-volt cable leading to the pulverizer feed amplifier and instead of the correct cables, which were 6 meters away. Employee #1 was electrocuted. (He was later pronounced dead at the scene by the coroner.) Employee #2 jumped back from the resulting electrical fault and struck his arm against a condenser pipe.

Keywords: ELECTRICAL, ELECTRIC CABLE, ELECTRICIAN, ELECTROCUTED, LOCKOUT, E GI IV, INSULATED TOOL, HAND TOOL, STRUCK AGAINST, ELECTRICAL WORK

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 761080 Occupation Not Listed
2 761072 Occupation Not Listed
3 761064 Occupation Not Listed
4 761056 Fatality Electric Shock Electricians
5 761056 Non Hospitalized injury Bruise/Contus/Abras Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.