Accident Summary Nr: 14481212 - COAL TAR PITCH DUST EXPLOSION AND FIRE

Accident Summary Nr: 14481212 -- Report ID: 0316400 -- Event Date: 08/10/1984
Inspection NrDate OpenedSICNAICSEstablishment Name
115168708/20/198433340Kaiser Aluminum & Chemical Corp

Abstract: CRUSHED COAL TAR PITCH HAD JAMMED IN A "BRADY" CONVEYOR SYSTEM. TWO EMPLOYEES, ALONG WITH TWO FOREMEN, HAD GONE TO THE BASEMENT OF THE BUILDING AND REMOVED A SECTION OF THE PIPE. THEY WERE GOING TO INCREASE AIR PRESSURE IN THE LINE TO PURGE THE MATERIAL BY BLOWING IT OUT AT THE POINT WHERE THE PIPE HAD BEEN DISCONNECTED. THIS WAS A COMMON PRACTICE AND WAS THE SECOND TIME IT HAD BEEN DONE ON THIS SAME SHIFT. WHEN THE LINE CLEARS ITSELF THE ENTIRE BUILDING IS ENGULFED IN COAL TAR DUST. THE AREA HAD NOT BEEN CLEANED IN OVER TWO WEEKS, ALLOWING AN UNUSUAL AMOUNT OF PITCH TO BUILD UP IN THE BASEMENT. THE TWO FOREMEN (MAINTENANCE) TOLD THE TWO MILLWRIGHTS TO GO ON BREAK WHILE THEY BLEW OUT THE PLUGGED LINE. THE MILLWRIGHTS LEFT. WHILE ONE OF THE FOREMEN WAS AT THE AIR CONTROL VALVE, PRESSURIZING THE SYSTEM TO BLOW OUT THE PLUG, A CLOUD OF DUST AND A BALL OF FIRE CAME UPSTAIRS AND OUT OF THE BASEMENT. THERE WAS INSTANTLY A FLASH FIRE IN THE BUILDING. THEN A MAJOR FIRE BROKE OUT AS THE PITCH RESIDUE, WHICH WAS EVERYWHERE, BEGAN TO BURN. THE TWO FOREMEN WALKED OUT OF THE BUILDING ON THEIR OWN, WITH MOST OF THEIR CLOTHING BURNT OFF THEM. BOTH HAD SECOND AND THIRD DEGREE BURNS OVER 70% OF THEIR BODIES. THE IGNITION SOURCE FOR THE EXPLOSION AND FIRE WAS MOST PROBABLY A BROKEN INCANDESCENT LIGHT BULB.

Keywords: BURN, COAL TAR PITCH, COAL DUST, FIRE, EXPLOSION, CONVEYOR, PURGING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 1151687 Fatality Burn/Scald(Heat) Occupation not reported
2 1151687 Fatality Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close