Accident Report Detail
Accident Summary Nr: 144744.015 - Employee burns hand after disconnecting nuts on pressurized
Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
---|---|---|---|---|
1585063.015 | 03/23/2022 | 238220 | American Refrigeration Usa |
Abstract: At approximately 9:00 a.m. on March 15, 2022, an employee disconnected nuts to a line for service and repair work. The employee was working to depressurize lines of ammonia for service work. The team had isolated, performed proper lockout/tagout, and bled the line assigned for work off. The employee began disconnecting nuts on the wrong line with pressure still on it. Upon breaking loose, the nut-pressurized ammonia began to leak from the pipe; the employee reacted to protect the plan and other personnel on-site, grabbed the nut, and manually screwed a few turns of the threads to stop the leaking. This action caused burns to the employee's hands that needed medical attention. The employee was not wearing his protective gloves because he was supposed to be working in the bled offline, which would have eliminated the hazard of glove use. The employee sustained burns to the right hand from the anhydrous ammonia and was hospitalized for these injuries.
Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury |
---|---|---|---|---|---|
1 | 1585063.015 | 30 | M | Hospitalized injury |