Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14429435 - ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC PUMP

Accident Summary Nr: 14429435 -- Report ID: 0830500 -- Event Date: 08/18/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
10061543408/18/198716220Ames Construction, Inc.

Abstract: AN EMPLOYEE WAS STANDING IN A WATER-FILLED DEPRESSION WITH A TURUMI SUBMERSIBLE PUMP (MODEL NUMBER NK-15). THE PUMP HAD ITS EQUIPMENT GROUNDING CONDUCTOR CONNECTED TO ONE OF THE CIRCUIT CONDUCTORS OF AN EXTENSION CORD SET; THUS, ITS FRAME WAS ENERGIZED. THE CORD SET WAS CONNECTED TO A GENERATOR TRAILER PROVIDING POWER TO THE PUMP. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, ELECTROCUTED, ELECTRIC PUMP, E C, GROUND FAULT, EQUIPMENT GROUNDING, WATER

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 100615434 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.