Powered by GoogleTranslate

Accident Report Detail

Accident Summary Nr: 14418941 - ELECTRIC SHOCK - CONTACT WITH ENERGIZED PARTS

Accident Summary Nr: 14418941 -- Report ID: 0728500 -- Event Date: 07/04/1994
Inspection NrDate OpenedSICNAICSEstablishment Name
10663361307/06/199449310Ozark Electric Cooperative

Abstract: Two power line workers were dispatched to a site in response to complaints from electric utility company customers. They arrived at the scene and traveled to a utility pole where they found an open fuse. They replaced the fuse. Seeing that the lights in two houses came on, the employees believed that they had repaired the power line and started to leave. However, the dispatcher radioed the employees that the company was still receiving complaints about outages on the line. The power line workers returned to the site, noting that lights were out past a certain point. The employees determined that the problem originated at a pad-mounted transformer located at a residence. They went to a different pad-mounted transformer, where they believed that they could deenergize the power line. However, they should have gone to a different transformer or to the pole where they had replaced the fuse to deenergize the line properly. Believing that they had deenergized the power line, the employees went to the problem transformer. They unlocked and opened the hinged transformer case. One of the power line workers crouched in front of the open transformer and began removing a faulty elbow. The other employee was holding a flashlight, and he was touching a fence, the first employee, and the transformer case. The employee working on the elbow touched it against wiring on a Y-elbow, energizing the case of the transformer. An electrical fault occurred; and the employee, realizing he had been burned by the ensuing electric arc, ran from the area and removed his glove. The other employee remained at the transformer, apparently unable to move. He later fell to the side of the transformer, possibly when the fuse at the utility pole opened the circuit. When the first employee realized the power was off, he ran to the assistance of his coworker and pulled him away from the transformer. A bystander administered cardio-pulmonary resuscitation, to no avail. The employee had been electrocuted.

Keywords: BURN, PROTECTIVE GROUNDING, ELECTRICAL, CPR, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, TRANSFORMER

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 106633613 Fatality Electric Shock Electrical power installers and repairers
2 106633613 Non Hospitalized injury Electric Shock Electrical power installers and repairers

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close