Accident Summary Nr: 14412407 - Two employees killed when powered platform falls

Accident Summary Nr: 14412407 -- Report ID: 0626600 -- Event Date: 05/26/1987
Inspection NrDate OpenedSICNAICSEstablishment Name
10070394105/26/198717990Scaffold Maintenance Company, Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
10229618305/02/198773490Rom, Inc.
Inspection NrDate OpenedSICNAICSEstablishment Name
10070388305/26/198765120Gerald D. Hines Interests
Inspection NrDate OpenedSICNAICSEstablishment Name
10070393305/26/198773490Jobs Building Services

Abstract: Employees #1 and #2 were using a powered platform to wash windows on the north slope of the Pennzoil Place Building. The powered platform they were working from was mounted on the half of the roof that was sloped at a 45 degree angle. The roof cars supporting the platform ran along a monorail that followed the horizontal and sloped halves of the roof. Two cables ran from the roof cars to hoisting motors beneath the platform. As the roof cars were traversing the monorail, a worn gear on the trailing roof car apparently gave way at the corner of the slope. The trailing car fell and struck the leading car, causing the units to speed down the sloped portion of the monorail and off the roof. Overspeed safety devices, designed to prevent this type of accident, were disabled and could not activate. The powered platform, with both employees tied off to it, fell about 37 stories to the street. Employees #1 and #2 were killed on impact. One pedestrian was killed and another was injured by the falling platform.

Keywords: WINDOW WASHER, EQUIPMENT FAILURE, ELEVATED WORK PLAT, GEAR, RAIL, FALL

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 100703941 Occupation Not Listed
2 102296183 Occupation Not Listed
3 100703883 Occupation Not Listed
4 100703933 Fatality Concussion Occupation not reported
5 100703933 Fatality Concussion Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close