Accident Summary Nr: 14383541 - ELECTRIC SHOCK - GROUND FAULT IN CORD CONNECTOR

Accident Summary Nr: 14383541 -- Report ID: 0524530 -- Event Date: 10/29/1993
Inspection NrDate OpenedSICNAICSEstablishment Name
10655732510/30/199333510Cerro Copper Products Co.

Abstract: A THREE-PERSON CREW WAS INSTALLING A CORD- AND PLUG-CONNECTED SUMP PUMP IN A PIT. ONE OF THE EMPLOYEES PICKED UP THE CONNECTOR ON THE END OF AN ENERGIZED 480-VOLT EXTENSION CORD SET AND THEN TOUCHED A GROUNDED METAL FIXTURE. HE WAS ELECTROCUTED. THE CORD SET WAS JOB MADE, AND AN UNGROUNDED CIRCUIT CONDUCTOR HAD BEEN CONNECTED TO A TERMINAL IN THE CONNECTOR THAT WAS INTENDED FOR THE EQUIPMENT GROUNDING CONDUCTOR.

Keywords: ELECTRICAL, CORD SET, E GI VII, ELECTROCUTED, GROUND FAULT, CORD CONNECTOR, EQUIPMENT GROUNDING

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 106557325 Fatality Electric Shock Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.